Operating Parameters
B-5
Part 1073401_07
E 2021 Nordson Corporation
10
Enable or Disable the Melter Password
Description:
Activates or deactivates the melter password. When password protection
is activated, component setpoint temperatures or melter operating
parameters cannot be changed until a valid password is entered using
parameter 0.
Value:
0 (disabled)
1 (enabled)
Resolution:
—
Default Value:
0
Format:
—
Use:
A password must first be created using parameter 11 before it can be
enabled or disabled using parameter 10.
11
Create Password
Description:
A user-defined password that prevents unauthorized changes to
operating parameters or setpoint temperatures.
Value:
0 to 9999
Resolution:
1
Default Value:
5000
Format:
—
Use:
Refer to Section 4, Operation, Entering the Melter Password.
NOTE: When the password is created and enabled, parameter 10 will not
appear again in the right display until the password is entered.
12
Change Hose 1 Output to Electric Applicator
Activation
Description:
Changes the proportioned 240 VAC current that is provided to the hose 1
heater to a switched 240 VAC current that is used to activate a
manifold-mounted electric applicator.
Value:
0 (disabled)
1 (enabled)
Resolution:
—
Default Value:
0 (disabled)
Format:
—
Use:
Use only when a Nordson manifold-mounted electric applicator is
installed and a switching device is connected to the melter’s switch
receptacle. Refer to the electric applicator manual for information on
mounting and using the applicator.