Installation, Operation and Maintenance Manual
20
7.6. P06 Off Line cleaning Cycles
OFF_LINE_CLEAN_C
PO6_____XX_CYCLES
Once the fan set is switched off, Off Line Cleaning is initiated and completes the number of cycles
selected here. You can choose anything between 0 and 15 cycles. If the setting is “0”, Off Line Cleaning
is switched off.
7.7. P07 Star/Triangle switch over Time
ST_TR_SW_TIME___
P07______XXX_SEC
After the fan set is switched on, outputs K1 (mains contactors) and K3 (star contactors) are activated.
At the end of the star/triangle switch-over time, output K3 (star contactor) is switched off, and output
K2 (triangle contactor) is activated with a delay of approximately 0,5 seconds.
7.8. P09 Cleaning Pulse interval 1
PULSE_INTERVAL_1
P09______XXX_SEC
Cleaning Pulse interval is the time in seconds between cleaning pulses when cleaning is operational.
7.9. P12 Cleaning valve Pulse time
CLEAN_PULSE_TIME
P12_______XXX_MS
The pulse time for the cleaning valves is the time for which the solenoids are energised each pulse.
Factory default setting is 100 milliseconds – this is suitable for most Afterfilter types however please
refer to the specific installation and operation manual for your unit type to verify the correct pulse time
and adjust this parameter if required.
7.10. P15 display Language
DISPLAY_LANG_____
P15_______ENGLISH
The display text can be output in eight different languages. The default language is English, but you can
also choose one of following languages: German, French, Dutch, Italian, Spanish, Danish, and
Swedish. The set language will be used in all menu’s and modes.