Installation, Operation and Maintenance Manual
25
7.22. P50 Back To Factory Settings
FACTORY_SETTINGS
P50__________YES
FACTORY_SETTINGS
P50______CONFIRM
With this parameter the system will reset all the parameters as described in the next table to default
factory settings.
Code Description Display line Factory settings
P02 Delta P Min
DP_MIN__________
P02_____XXX_daPa
40 daPa
P03 Delta P Max
DP_MAX__________
P03_____XXX_daPa
80 daPa
P04 Delta P Max Alarm
DP_MAX_ALARM____
P04_____XXX_daPa
150 daPa
P05 Low Pressure Alarm
LOW_PRESS_ALARM_
P05_____XXX_daPa
0 daPa
P06 Off line Cleaning cycles
OFF_LINE_CLEAN_C
P06____XX_CYCLES
0
P07 Star/Triangle switch over time
ST_TR_SW_TIME___
P07______XXX_SEC
5 s
P09 Cleaning Pulse interval 1
PULSE_INTERVAL_1
P09______XXX_SEC
10 s
P12 Cleaning valve Pulse time
CLEAN_PULSE_TIME
P12_______XXX_MS
100 ms
P22 Delta P Cleaning mode
DP_CLEAN_MODE___
P22_2_STOP_&_END
Stop and End
The settings will be reset by pressing the enter button for more then 2 seconds. The system will ask
for a confirmation after which the enter button needs to be pressed again for more then 2 seconds.
7.23. M05 Total Operating Hours
TOTAL_OPERAT_H__
M05_xxxxxx_HOURS
Display of active operating hours (with running fan) of the control box since start-up.