Table 7. Charging Table for 3.5 Ton Models
S4BE-042KA SERIES
SUCT.
PRESS.
OUTDOOR TEMPERATURE (°F)
70 75 80 85 90 95 100 105
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
128 238 120
130
239 125
260 124
132 239 129
261 128
282 127
134
240 133
261 132
282 131
304 130
136 240 137
262 136
283 135
304 134
326 134
138 262 140
284 139
305 138
326 137
348 137
140 284 143
306 142
327 141
348 141
370 140
142 306 145
327 144
349 144
370 144
392 144
144 307 149 328 148
349 147
371 147
392 147
146 329 151 350 151
371 150
393 150
148 350 154 372 154
393 153
150 372 157 394 156
152 394 160
154
S4BE-036KA SERIES
SUCT.
PRESS.
OUTDOOR TEMPERATURE (°F)
70 75 80 85 90 95 100 105
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
129 232 124
131
233 127
255 125
133 233 131
255 129
278 127
135
234 135
256 132
278 131
300 129
137 234 140
257 136
279 134
301 132
323 131
139 257 141
279 138
302 135
324 134
346 132
141 280 142
302 139
324 137
347 135
369 134
143 303 143
325 140
347 139
369 137
392 135
145 303 146 326 144
348 142
370 140
392 138
147 326 147 348 145
371 143
393 142
149 349 148 371 146
393 144
151 372 149 394 147
153 395 149
155
Table 6. Charging Table for 3 Ton Models
Shaded boxes indicate flooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air flow, entering dry
bulb, or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
3. In Cooling Mode, suction pressure will be lower than design value if indoor air flow, entering dry bulb, or entering
wet bulb temperatures are lower than design.
4. In Heating Mode, charge should be weighed in. It is strongly recommended to verify charge in cooling mode at
ambient above 70°F.