EasyManuals Logo

Nordyne VG7TC-FS User Manual

Nordyne VG7TC-FS
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
13
Outdoor Terminations - Vertical Venting
Termination spacing requirements from the roof and from
each other are shown in Figure 10 (page 13). The roof
penetration must be properly flashed and waterproofed
with a plumbing roof boot or equivalent flashing. Vent
and combustion air piping may be installed in an existing
chimney which is not in use provided that:
• Boththeexhaustventandairintakerunthelengthof
the chimney.
• Thetopofthechimneyissealedandweatherproofed.
• The termination clearances shown in Figure 10 are
maintained.
• Noothergasredorfuel-burningequipmentisvented
through the chimney.
Vent Freezing Protection
CAUTION:
Whentheventpipeisexposedtotemperatures
below freezing (i.e., when it passes through
unheated spaces, chimneys, etc.) the pipe
mustbeinsulatedwith1/2inchthicksponge
rubberinsulation,Armaex-typeinsulationor
equivalent.Insulatingpipeisimportanttoavoid
condensateicing.
• Table 2 (page 14) lists the maximum length of flue
pipe that can travel through an unconditioned space or
an exterior space. The total vent length must not exceed
the lengths noted in Table 1 (page 11). For Canadian
installations, please refer to the Canadian Installation
Code (CAN/CGA-B149.1 or 2) and/or local codes.
• Forextremelycoldclimatesorforconditionsofshort
furnace cycles (i.e. set back thermostat conditions) the
last 18 inches of vent pipe can be reduced. It is acceptable
to reduce from 3” to 2-1/2”, 3” to 2”, or 2” to 1-1/2” if
the total vent length is at least 15 feet in length and the
vent length is within the parameters specified in Table 1.
The restriction should be counted as 3 equivalent feet.
Smaller vent pipes are less susceptible to freezing, but
must not be excessively restrictive. The length of the 2
inch pipe must not be longer than 18 inches.
• Iffurnaceisinstalledhorizontally,makesurethedrainage
port on the in-line drain assembly is pointed downward
to ensure proper drainage of condensate. See Figure
38 (page 47).
• To prevent debris or creatures from entering the
combustion system, a protective screen may be installed
over the combustion air intake opening. The screens
hole size must be large enough to prevent air restriction.
• Foroptimalperformance,ventthefurnacethrougha
wall that experiences the least exposure to winter winds.
• The vent termination shall be located at least 3 ft.
horizontally from any electric meter, gas meter, regulator
and any relief equipment. These distances apply ONLY
to U.S. installations. In Canada, CSA B149.1, takes
precedence over these instructions.
• Do not install the vent terminal such that exhaust is
directed into window wells, stairwells, under decks
or into alcoves or similar recessed areas, and do not
terminate above any public walkways.
• Ifventinghorizontally,asidewallventkitisavailable
according to the pipe diameter size of the installation.
For 2 inch pipe use side wall vent kit #904617, and
for 3 inch pipe use kit #904347. Please follow the
instructionsprovidedwiththekit.
• Concentricventterminationkitsareavailableforuse
with these furnaces. For 2 Inch pipe use kit #904952
and for 3 inch pipe use kit # 904953. Pleasefollowthe
instructionsprovidedwiththekit.
• Whentheventpipemustexitanexteriorwallcloseto
the grade or expected snow level where it is not possible
to obtain clearances shown in Figure 7, a riser may be
provided as shown in Figure 9. Insulation is required
to prevent freezing of this section of pipe. See Table 2
(page 14) for vent freezing protection.
Support
NOTE: Vent Configuration to Provide
12" Minimum height above Snow Level.
1/2"
Armaflex
Insulation or
Equivalent
(if required)
12" Above
Maximum
Expected
Snow Level
19" Max.
(See Note)
Outside
Wall
Figure9.Alternate Horizontal Vent Installation
Figure10.VerticalVentTermination
Combustion Air
Exhaust Vent
12” Above Maximum
Expected Snow Level
(Both pipes)
Elbows on the combustion air
inlet must be positioned pointing
away from the exhaust vent.
8" Min.
36" Max.
Plumbing Vent Roof Boot
(Both Pipes)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nordyne VG7TC-FS and is the answer not in the manual?

Nordyne VG7TC-FS Specifications

General IconGeneral
BrandNordyne
ModelVG7TC-FS
CategoryFurnace
LanguageEnglish

Related product manuals