108 AFP-200 Instruction PN 15511:F2 10/11/99
Sensitivity allows the operator to change the sensitivity of any addressable detector in the system.
Det. Sensitivity Enter point: AA, E
Now enter the address of the detector you wish to change. Example Detector 57.
D 5 7
D57 now Low sens. Enter H, M, or L to change, Esc. to Abort
Clear Verification enables the operator to clear the verification counter for all the addressable detectors in the
system.
3 ENTER
Press Enter to Clear Verification Counts or Esc. to Abort
Clear History allows the operator to clear the entire history buffer.
4 ENTER
Press Enter to Clear History or Esc. to Abort
Set Action/Alert enables the operator to set the AWACS Alert and Action levels.
5 ENTER
Set % of Alarm: Alert(T) and Action(N) Format: TxxNxx then
Enter
Enter the Alert and Action AWACS levels. Example: Alert level=50% and the Action level=70%
T 5 0
2 ENTER
ENTER
ENTER
T50N70
N 7 0