AFP-200 Instruction PN 15511:F2 10/11/99 109
CRT-2 Configuration
The CRT-2 must be set up to communicate with the control panel using the proper protocol. To enter the setup
menu on the CRT-2, hold down the CTRL button while pressing the SCROLL LOCK key. There are thirteen
groups of parameters that must be set. Each of these thirteen groups is reached by pressing the corresponding
function key (F1 – F13). Use the arrow key to move through each setup group and use the space bar to view the
options for each parameter.
F1
Emulation=Wyse-50+ Comm Mode=Full Duplex EIA Baud Rate=2400
Aux Baud Rate=2400 Enhanced=On EIA Data Format=7/1/E
Aux Data Format=7/1/E Language=U.S. Sessions=One
Host/Printer=EIA/Aux
F2
Emulation=Wyse-50+ Enhanced=On Auto Wrap=Off
Auto Font Load=On Auto Page=Off Auto Scroll=On
Monitor Mode=Off Screen Saver=Off Bell Volume=09
Warning Bell=On Host/Printer=EIA/Aux Sessions=One
F3
Page Length=24 Screen Length=26 Lines Screen Video=Normal
Display Cursor=On Cursor=Blink Block Auto Adjust Cursor=On
Columns=80 Width Change Clear=Off Speed=Normal
Scroll=Jump Refresh Rate=60 Hz Overscan Borders=Off
F4
Language=U.S. Char Set Mode=PC Key Mode=ASCII
Keyclick=Off Key Repeat=Off Margin Bell=Off
Key Lock=Caps
F5
Enter Key=<CR> Return Key=<CR> Backspace=<BS>/<DEL>
Alt Key=Meta Desk Acc=Disabled Pound Key=U.S.
F6
EIA Baud Rate=2400 EIA Data Format=7/1/E EIA Parity Check=On
Aux Baud Rate=2400 Aux Data Format=7/1/E Aux Parity Check=On
EIA Xmt=Xon-Xoff EIA Recv=Xon-Xoff(XPC) EIA Xmt Pace=Baud
Aux Xmt=Xon-Xoff Aux Recv=Xon-Xoff(XPC) Aux Xmt Pace=Baud
EIA Break=Off EIA Modem Control=Off EIA Disconnect=2 sec
Aux Break=Off Aux Modem Control=Off Aux Disconnect=2 sec
F7
Comm Mode=Full Duplex Local=Off Recv <CR>=<CR>
Recv <DEL>=Ignore Send ACK=On Send Line Term=<US>
Send Block Term=<CR> Null Suppress=Off