AFP-200 Instruction PN 15511:F2 10/11/99 97
Receiving Unit
For applications requiring transmission of burglary alarm information to a central receiving unit, the control
panel may be connected to an AM2020 or AFP1010 provided with a NIB-96 network interface board (for wiring
information, refer to Appendix B). The AM2020/AFP1010 must be configured for Combination Fire/Security
applications as defined in Installation section of the AM2020/AFP1010 manual. Burglar alarm zones are
reported to the AM2020/AFP1010 through the NIB-96 Network Interface Board. The AM2020/AFP1010
networked monitor points must be programmed as SARM type code (security alarm).
Programming
The control panel may select any number of Burglar Alarm type code devices using the programming menu and
point submenu. Select the address of an MMX Monitor Module used for security, and set the MMX type code
to BURGLAR ALA.
Circuit Wiring
Wire security monitoring zones as shown in Figure E-2, “Typical Protected Premises Wiring for Central Station
and Proprietary Burglar Alarm Applications.”
LED Indicators
The AFP-200 is supplied with a unique security keypad slide-in label for combination fire/burglary applications.
This security label is identical to the standard slide-in label, except the fourth label position shows Security
rather than Supervisory. (Combination fire/burglary listing does not include supervisory service.) On any
burglar alarm, the Supervisory LED, as well as normally-open contacts on TB3 terminal 1 and TB3 terminal 2,
will activate.
Combination Fire/Burglary Applications