Before connecting a loop to an LCM or LEM card, carry out the following tests:
1. Check loop continuity and resistance by placing a short circuit on one end of the loop and reading the loop
resistance with a multimeter at the other (be sure to set the multimeter to Ohms). The loop resistance cannot
exceed 50 Ohms which is 25 ohms per leg. Refer to note below if using ISO-X modules.
2. Check devices for correct wiring as follows. With both ends of the circuit open, set the multimeter to diode test,
and place the leads on the cable, the reading should be approx. 0.645, reverse the leads to get a reading of
approximately 1.2 or higher. If both readings are low, there is an incorrectly wired device, or a short on the
wiring. (Note: Each device has a diode installed)
3. Check the loop voltage as follows. Set the multimeter to D.C. volts and read the voltage at the loop card before
connecting the loop. The reading should be 24 - 25 volts. Now connect the loop. The reading should be 15-16
volts. If the measured voltage goes below this value, there could either be a short on the line or a device may
be incorrectly wired (possible reverse polarity). Find the device and correct the loop connections at that device.
4. Check that there are no earth faults as follows. Select ohms on the multimeter and measure between each leg
of the loop and earth. If the reading falls below 50,000 ohms, an earth fault will be indicated when the loop is
connected. Find the cause of the earth fault and rectify it. (Note: Possible causes of an earth fault are
moisture, inadequate insulation from the surrounding building, equipment or materials).
NOTE: Loop resistance measurement when ISO-X isolation modules are present:
When power is removed from the loop, the positive side of the circuit is opened at each ISO-X isolation
module. To measure the loop resistance, temporarily place a jumper between Terminals 2 and 4 on each
ISO-X while taking measurements. Remember to remove all the jumpers and test all isolator modules
when you have finished taking the readings.
www.PDF-Zoo.com
firealarmresources.com

Table of Contents

Other manuals for Notifier AFP-2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-2800 and is the answer not in the manual?

Notifier AFP-2800 Specifications

General IconGeneral
BrandNotifier
ModelAFP-2800
CategoryControl Panel
LanguageEnglish

Related product manuals