EasyManuals Logo

Notifier AFP-3030 Programming Manual

Notifier AFP-3030
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #123 background imageLoading...
Page #123 background image
AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 117
Equations CBE: Zones and Equations
Example: NOT(Z02)
The logic zone will remain activated until the argument activates.
If the argument activates the logic zone will deactivate.
The “ONLY1” Operator
Requires that only one argument be active.
Example: ONLY1(Z02,Z05,Z09)
If only one of the arguments activates the logic zone will be activated.
The “ANYX” Operator
Requires that the amount of arguments specified by the number preceding the arguments be
active.
Example: ANYX(2,Z02,Z05,Z09)
If any two or more of the arguments are in alarm the output point will be activated.
The X amount may be a value from 1 through 9.
The “XZONE” Operator
Requires that any combination of two or more input devices programmed to a zone be active.
Example: XZONE(Z02)
If any combination of two or more initiating devices that have been mapped to this software
zone come into alarm, then outputs mapped to this zone will activate.
The “RANGE” Operator
Each argument within the range must conform to the requirements of the governing function.
The range limit is 20 consecutive arguments.
Example: AND(RANGE(Z1,Z20))
Zone 1 through Zone 20 must all be active to activate the logic zone.
The “DIS(point argument)” Operator
Requires that the point argument be disabled for the operator to go active.
The “PRE(point argument)” Operator
Requires that the point argument be in prealarm for the operator to go active.
Example: AND(L1D1,PRE(L1D2))
The detector at address L1D1 must be active and the detector at L1D2 must be in prealarm for
this equation to go active.
The “SUP(point argument)” Operator
Requires that the point argument be in an active supervisory state for the operator to go active.
Example: OR(L1D1,SUP(L1M1))
The detector at address L1D1 must be active, or the module at L1M1 must be in an active
supervisory state, for the equation to go active.
The “FIRE(point argument)” Operator
Requires that the point argument be in an active fire alarm state for the operator to go active.
Example: AND(L1D1,FIRE(L1M1),FIRE(L1M2))
The detector at address L1D1 must be active, and the modules at L1M1 and L1M2 must be in
an active fire alarm state, for the equation to go active.
The “NON(point argument)” Operator
Requires that the point argument be in an active non-alarm state for the operator to go active.
Example: AND(L1D1,NON(L1M1))
NOTE: Local General Zones only.

Table of Contents

Other manuals for Notifier AFP-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-3030 and is the answer not in the manual?

Notifier AFP-3030 Specifications

General IconGeneral
BrandNotifier
ModelAFP-3030
CategoryControl Panel
LanguageEnglish

Related product manuals