30 AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015
PrealarmProgram Panel Program
3.2.5 Panel Timers (Menu 1)
Press the Panel Timers soft key on the Panel Program Menu 1 screen to display the following
screen.
Figure 3.16 Panel Timers (Menu 1) Screen
Soft Keys
VERIFY TIME: Press this soft key to set the Alarm Verification timer. Type in a value of 0-60
(seconds), which will delay initiating devices set for Alarm Verification from signalling for the
amount of time entered. If a second alarm occurs while the alarm verification timer is counting, the
timer will stop and the alarm will signal immediately. Default: 30
MAXIMUM VERIFICATION COUNT: Press and enter a value from 0-20 for a maximum
verification count threshold value that applies to detectors set to participate in Alarm Verification.
A value of zero produces no verification fault. When the counter exceeds the threshold value
entered, a fault is generated to the panel. Default: 00
SILENCE INHIBIT: Press to enter a value from 0 (disabled) to 5 minutes. This software timer
disables the SIGNAL SILENCE key function for the time entered when a fire alarm occurs. The
timer starts at the first alarm only; it does not restart with each new alarm. Default: 0
AUTO SILENCE: Press to enter a value of OFF (no Auto Silence Timer), or a value of 10, 15 or
20 minutes. This global software timer functions like pressing the SIGNAL SILENCE key. For
example, if a value of 10 is entered, the control panel will silence all active outputs programmed as
silenceable after ten minutes. Default: 0FF
VERIFY=PREALARM: Press this soft key to enter Yes or No for displaying Prealarm during alarm
verification. Default: NO
3.2.6 Panel Timers (Menu 2)
Press the MORE soft key on the Panel Timers Menu 1 screen to display the following screen.