40 AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015
PrealarmProgram Panel Program
PRINTER: Press to scroll through the types of printer supervision: NONE, 40-COLUMN,
40-COLUMN SUPERVISED, 80-COLUMN, 80-COLUMN SUPERVISED, 40 GRAPHIC, 80
GRAPHIC, 80 GRAPHIC SUPERVISED. The printer will not be active if NONE is selected. If a
SUPERVISED selection is made, the printer will be supervised. Default: NONE
MORE: Press to bring up the second supervision screen.
ACCEPT: Press to save changes and return to previous menu.
Supervision Screen (MORE)
This screen appears when MORE is selected at the supervision screen.
Figure 3.23 MORE Supervision Screen
TERMINAL: Select NONE or LCD-80. (Default: NONE.) Select LCD-80 when a LCD2-80 is
connected to the panel.
NOTE: When changing from an 80-column or 80-column supervised to an 80 graphic or 80
graphic supervised printer (or vice-versa), settings must be changed at the printer. Refer to this
panel’s installation manual for the settings.
SUPERVISION
TERMINAL:LCD-80
ACCEPT
BACK
NOTE: When LCD-80 Terminal Supervision is on, CRT baud rate selections of 19200 and 57600
are disallowed.

Table of Contents

Other manuals for Notifier AFP-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-3030 and is the answer not in the manual?

Notifier AFP-3030 Specifications

General IconGeneral
BrandNotifier
ModelAFP-3030
CategoryControl Panel
LanguageEnglish

Related product manuals