AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 43
Panel Program Menu (2) PrealarmProgram
Loop Programming
Figure 3.27 Loop Programming Screen
Soft Keys
INSTALLED: Press this soft key to choose YES or NO, depending on whether an SLC is installed
at this address.
DETECTOR POLL: Press to select loop-polling mode. (See note below.)
MODULE POLL: Press to select loop-polling mode. (See note below.)
RAPID POLL: For CLIP mode only - enable or disable Rapid Poll for CLIP. This feature will poll
the first 20 modules more often to speed response on manual pull stations.
WIRING STYLE: Press to select the wiring style (OPEN or CLOSED) of the loop. If CLOSED is
entered when the wiring is OPEN, a fault message will be generated at the panel.
BLINK MODE: Press to enable (ON) or disable (OFF) detector LED blinking for this loop. If the
Loop is configured in FlashScan mode with Blink Mode enabled, all detector and module LEDs
will remain OFF. If the loop is configured in CLIP mode with Blink Mode enabled, the LEDs for
detectors and monitor modules will remain OFF while the control modules operate normally.
NOTE: FlashScan and CLIP Mode
Most FlashScan devices can be programmed to run in either CLIP or FlashScan mode. The types
cannot be mixed on a loop: for example, if Loop 1 is programmed with a FlashScan module poll,
CLIP modules may not be used on that loop.
A detector’s LEDs will light a steady green for several seconds while it is subjected to a detector test
during FlashScan polling. Each detector is tested this way on a regular basis. During the short time
the LEDs are on steady, the detector is not providing fire protection.