Page #77 background imageLoading...
Page #77 background image
AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 71
Autoprogram Menu PrealarmProgram
2. Physically install/uninstall the SLC devices.
3. Press the AUTOPROGRAM LOOPS soft key to run the Autoprogram. Existing information
will not be changed.
Autoprogram will find the devices/modules on the selected installed SLCs. It will compare the
information it finds during autoprogramming against any point information that may already be in
the database, and it will look for any addressing errors, such as two detectors with the same
address. If it finds a discrepancy or error, a screen will be displayed with the discrepant or incorrect
information and the programmer will be given the option of changing it.
Figure 3.59 Autoprogram Menu Screen
Soft Keys
AUTOPROGRAM LOOPS: Press to scroll through the options: ALL, 1+2, 3+4, 5+6, 7+8,
9+10. Stop at the desired option to select it.
ACCEPT: Press to autoprogram the selection. A confirmation screen will display asking the
programmer to confirm the autoprogram choice made (press the YES soft key to confirm). A screen
with the message AUTOPROGRAM IN PROGRESS will display until autoprogramming is complete.
AUTOPROGRAM MENU
AUTOPROGRAM LOOPS: ALL
ACCEPT
BACK

Table of Contents

Other manuals for Notifier AFP-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-3030 and is the answer not in the manual?

Notifier AFP-3030 Specifications

General IconGeneral
BrandNotifier
ModelAFP-3030
CategoryControl Panel
LanguageEnglish

Related product manuals