Using the CRT-2 for Read Status Appendix C: Remote Terminal Access
NFS-640 Operations Manual P/N 51334:B 10/03/2003 73
Display the Status of all Programmed Points
From the “Read Status” menu, select option 3 - Read All Points. The CRT-2 displays a list of the status
of all addressable detectors, modules, panel circuits, system parameters and software zones:
View the History Buffer
From the “Read Statusmenu select option 4 - History-Step. This option lets you step through the
History buffer one event at a time:
The first line that appears displays the number of events in the History buffer. Step through the History
buffer one event at a time by pressing the Next F5 or Prior F6 function keys.
Send the History Buffer to the CRT-2
From the “Read Statusmenu select option 5 - History-All. This option sends the entire History buffer
to the CRT-2, from most recent event to oldest event:
The semicolon, a control character in networking applications, separates the hour and minute of events
displayed from history. If events display as they occur, a colon separates the hour and minute.
View the Alarm History Buffer
From the “Read Status” menu select option 6 -Alarm-History:Step. This option lets you step through the
Alarm History buffer one event at a time:
The first line that appears displays the number of events in the History buffer. Step through the Alarm
History buffer one event at a time by pressing the Next F5 or Prior F6 function keys.
NORMAL SMOKE(PHOTO) DETECTOR ADDR 1D001 Z03 Z Z Z Z 000%A5 PA:0 ** L1D001
NORMAL SMOKE(ION) DETECTOR ADDR 1D002 Z02 Z Z Z Z 00%A5 PA:0 ** L1D002
NORMAL HEAT(ANALOG) DETECTOR ADDR 1D003 Z01 Z Z Z Z 000%A5 PA:0 * L1D003
OFF CONTROL MODULE ADDRESS 1M049 Z00 Z Z Z Z IS* L1M049
NORMAL MONITOR MODULE ADDRESS 1M050 Z06 Z Z Z Z L1M050
Press
3W
EVENT History Start Events in HIST:005
Press
4W
Press
5W
************************** EVENT HISTORY **************************************
System Normal 04;15P Wed 07/07/01
SYSTEM RESET 04;15P Wed 07/07/01
ALARM SILENCED 04;15P Wed 07/07/01
ACKNOWLEDGE 04;14P Wed 07/07/01
ALARM: PULL STATION MODULE ADDRESS 1D151 Zone 06 04;14P 07/07/01 M151
************************** PRINT END *****************************************
Semicolon
Press
6W
************************** ALARM HISTORY START *************************************
ALARM: MAN_RELEASE MODULE ADDR 1M065 10:21A 050501 1M065
ALARM: MAN_RELEASE MODULE ADDR 1M065 10:19A 050501 1M065
ALARM: MAN_RELEASE MODULE ADDR 1M065 03:20P 050401 1M065
ALARM: SMOKE (ION) DETECTOR ADDR 1D129 03:20P 050401 1D129