EasyManua.ls Logo

NTI FTVN - Air Elimination Device; Low Water Cut-Off (Field Supplied); Applications

Default Icon
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25
Part 1 - General Safety Information
Part 4 - Water Piping
I. Applications*
G. Air Elimination Device
A micro bubble air elimination device must be installed in every boiler
installation. Automatic air vents alone are not an acceptable substitute
for a micro bubble air elimination device. Here are a few examples of
acceptable devices.
Spirovent
TACO 4900 Series
Cale Discal
In mixed temperature applications, mixing valves are required for the
protection of low temperature loops.
CAUTION
Figure 12 - Low Water Cut-O Basic Installation
Figure 13 - Piping Symbol Legend
H. Low Water Cut-O (Field Supplied)
This boiler is provided with a factory installed Water Pressure Switch. In the
event water pressure drops below 7 PSI, the control will go to a blocking
error “FILL - 108”, inhibiting burner operation.
However, a low water cut-o may be required by local codes. This is to be
remote-mounted and eld supplied. See Figure 12 for basic Low Water
Cut-O installation instructions. Do not install an isolation valve between
boiler and low water cut-o.
When wiring the low water cut-o follow the installation instructions
provided by the low water cut-o manufacturer.
NOTE: During a low water condition, the eld supplied low water cut-o
normally open contacts must break the main power supply to the boiler.
Failure to follow this instruction will defeat the purpose of a low water cut-
o and will result in damage to the boiler. Such damages are not covered
by boiler warranty.

Table of Contents

Related product manuals