EasyManua.ls Logo

NTI FTVN - Complete Menu Parameters

Default Icon
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
67
Part 9 - Controls
Menu
Sub-Menu
Parameter
Description Value
Default
Setting
2 3 BOILER CH PARAMETERS  1
2 3 1 Adjustable max CH power percentage 0 - 100 100
Limited by the absolute values
dened by parameters 2.3.3 and
2.3.4, i.e., 0 = min power and 100
= max power.
2 3 2
Absolute Max DHW power percentage
CANNOT BE MODIFIED
0 - 100
RESERVED FOR TECHNICAL
ASSISTANCE
Only if the gas or PCB is
changed. See Table 31.
2 3 3
Absolute Min boiler power percentage
CANNOT BE MODIFIED
0 - 100
2 3 4
Absolute Max CH percentage
CANNOT BE MODIFIED
0 - 100
2 3 5 CH Anti-cycling time mode 0 = Manual, 1 = Automatic 1
2 3 6
CH Anti-cycling Ignition Time Delay
(when 2.3.5 = 0)
0 - 7 (minutes) 3
2 3 7 Boiler Pump Post Circulation Time (After CH)
0 - 15 minutes or OC (On Conti-
nuously)
3
2 4 BOILER PARAMETER  PART 2
2 4 3 CH Fan Post-Purge 0 = 2 minutes, 1 = 5 minutes 1
2 4 4
CH Boost Interval 0 - 60 (minutes) 16 Only applicable when the type
of temperature control is set to
Basic Temp. Control
(Parameter 4.2.1 - 5.2.1 - 6.2.1
= 1)
Sets the time delay between the automatic adjustments of the boiler target temperature in
increments of +/- 7°F.
2 4 7 CH Pressure Safety 1 = pressure switch at minimum 1
RESERVED FOR TECHNICAL
ASSISTANCE
Only if the PCB is changed
2 4 9 Outdoor Temperature Reading Correction -5 - +5 (°F) 0
Only active with outdoor sensor
connected
2 5 DOMESTIC HOT WATER PARAMETER
2 5 0
DHW COMFORT function
0 = deactivated, 1 = timed,
2 = always on
0 -
Combi
2 -
Boiler
FTVN Non-Combi models set to 2 – Always On = This is not changeable.
FTVN Combi models set to 0 – Deactivated = COMFORT function is not active.
FTVN Combi models set to 1 or 2 – On (activates conditionally once per Comfort Anti-cycling Time) = Activating the COMFORT
function keeps the DHW heat exchanger temperature warm when a DHW demand is not active. This reduces the amount of time it
takes for the boiler to meet a hot water demand. COMFORT will display when this function is active.
NOTE: Parameter 251 ”Comfort Anti-cycling Time, is defaulted to 60 min, and has a range [0 -120] min.
2 5 1 DHW Comfort Anti-cycling Time 0 - 120 (minutes) 60
2 5 2 DHW Start Delay 5 - 200 (0.5 to 20 seconds) 5 Anti “water hammering”
2 5 3 DHW Switch O Logic
0 = anti-scale (stop at > 144°F)
1 = + 7 °F /setting
0
2 5 4
DHW Post Purge and Pump Cycle 0 = OFF, 1 = ON 1
OFF = 30 second post-circulation and 2 minute post-ventilation (or 3 minute post-circulation and 5 minute post-ventilation if the
boiler temperature requires it)
ON = When setting is ON, time for post-circulation is 3 minutes, while the time for post-ventilation is 5 minutes.
2 5 5 CH Start Delay Following DHW 0 - 30 (minutes) 0
2 5 7
Anti-legionella Function
0 = OFF
1 = ON
0
FTVN Non-Combi = Activated
when the boiler is connected to
a tank by an NTC sensor.
(Parameter 228 = 1)
This function prevents the formation of Legionnaires disease bacteria which may develop in piping and indirect water heaters
(IWH) at temperatures between 68°F and 104°F. When activated, if the IWH temperature stays below 138°F for over 100 hours, the
boiler will heat the water in the IWH until it reaches 149°F for 30 minutes.

Table of Contents

Related product manuals