EasyManua.ls Logo

NTI FTVN - Page 68

Default Icon
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
68
Menu
Sub-Menu
Parameter
Description Value
Default
Setting
2 5 8 Antilegionella frequency 24 - 720 (Hours), or 30 days
30
days
FTVN Non-Combi = Activated
when the boiler is connected to
a tank by an NTC sensor.
(Parameter 228 = 1)
2 6 BOILER MANUAL SETTINGS Only to test components
2 6 0 Manual mode activation 0 = OFF, 1 = ON 0
2 6 1 Boiler pump control 0 = OFF, 1 = ON 0 Set Parameter 260=1
2 6 2 Fan control 0 = OFF, 1 = ON 0 Set Parameter 260=1
2 6 3 3 way valve control 0 = DHW, 1 = Heating 0 Set Parameter 260=1
2 7 TEST & UTILITIES
2 7 0 Test Mode
TEST+ = Max Heating power
TEST+ = Max DHW power
TEST+
= Minimum power.
TEST Mode can also be activated
by pressing the Reset button
for 10 seconds. Test Mode
deactivates after 30 minutes or
by pressing Reset.
2 7 1 Air-purge cycle 0 = OFF, 1 = ON See First Ignition section.
2 7 4 Floor drying cycle
0 = OFF
1 = Functional Heating
2 = Curing Heating
3 = Functional Heating + Curing
Heating
4 = Curing Heating + Functional
Heating
5 = Manual
0
2 7 5 Floor dry Supply setpoint temperature 77 - 140°F 131
2 8 RESET FACTORY SETTINGS
2 8 0
Automatically resets all parameters to the factory
defaults.
WARNING: Always check PCB settings if restoring
factory default settings on a replacement
controller. Replacement controllers have generic
settings that may not be specic to the boiler
model.
Reset: OK = yes, ESC = no
To Reset all parameter settings,
press the OK button.
2 10 0 CH On Dierential Temperature 0 - 36
o
F 11
Determines how much the boiler
outlet temperature can drop
below target before turning the
boiler back on.
2 10 1 DHW Modulation Setpoint 68 - 179
o
F 179
Boiler target temperature during
a DHW demand. Not applicable
for Combi models.
2 10 2 DHW On Dierential Temperature 0 - 36
o
F 0
Determines how much the
DHW storage tank temperature
can drop below target before
initiating a DHW demand. Only
applicable when 2.2.8 = 1.
2 10 3 Emergency Setpoint 68 - 179
o
F 113
Sets Follower boiler
operating temperature when
communication with the Master
is lost, or when the System
Sensor is disconnected. See
Cascade Instruction Manual.
2 10 4 CH/DHW Shifting Priority Timer 0 - 1440 minutes 45
Determines how long a CH or
DHW demand can last before
the priority is switched. First
priority is with DHW. A value of
0 keeps the priority with DHW
indenitely.
Part 9 - Controls

Table of Contents

Related product manuals