70
Menu
Sub-Menu
Parameter
Description Value
Default
Setting
4 2 3
Parallel Shift of Reset Curve
-12 - +12 (when 4.2.0 = 0)
0
See K. Parallel Shift of Reset
Curve.
-25 - +25 (when 4.2.0 = 1)
When the Reset Curve results in a boiler target temperature that is too high or too low
(i.e., heats the building too quickly or slowly), Parallel Shift can be used to oset the
curve up or down to increase or decrease the boiler target temperature.
NOTE: Adjusting Parallel Shift is only possible when Auto Boost is OFF (4.7.5 = 0).
The Parallel Shift can be adjusted from the home screen using the CH + and - buttons
(Figure 57, Item 8).
With the rst press of the CH + or - button, the display shows the current CH target
temperature (e.g., 130
o
F).
After a 3-5 second delay, the display begins ashing the current oset (Parallel Shift)
setting. Subsequent CH + or - button presses adjusts the oset up or down.
After a few seconds the display shows the new CH target temperature (e.g., 138
o
F), then
returns to the home screen.
AUTO
1
4 2 4
Room Sensor Inuence 0 - 20
2 if Parameter 4.2.0 = 0
4 if Parameter 4.2.0 = 1
Adjusts the inuence of room temperature on target boiler temperature - a higher setting causes a greater increase to the boiler
target temperature as the indoor temperature drops below room setpoint. Only applicable when using an optional NTI Room
Sensor and when 4.2.1 = 2 or 4.
4 2 5
MAXIMUM Temperature Setting
86 - 179 °F 179 if Parameter 4.2.0 = 1
68 - 122 °F 120 if Parameter 4.2.0 = 0
4.2.5 sets the allowable boiler operating temperature range for Zone 1 heating, limiting Automatic Temperature Control and
manual adjustments from the User Menu.
4 2 6
MINIMUM Temperature Setting
86 - 179 °F 120 if Parameter 4.2.0 = 1
68 - 122 °F 80 if Parameter 4.2.0 = 0
4.2.6 sets the allowable boiler operating temperature range for Zone 1 heating, limiting Automatic Temperature Control and
manual adjustments from the User Menu.
4 3 ZONE 1 DIAGNOSTICS
4 3 0 Room Temperature Read only
Only applicable when using an
NTI room sensor
4 3 1 Room Temperature Setpoint Read only
4 3 4 Heat Call 0 = OFF, 1 = ON (Read only)
4 7 ZONE 1 REGULATION PARAMETERS
4 7 5 Auto Boost 0 = OFF, 1 = ON 0 See L. Auto Boost.
5 ZONE 2 PARAMETERS
5 0 ZONE 2 TEMPERATURE SETTINGS
5 0 0 Temperature Day 50 - 86 °F 66
Only applicable when using an
NTI room sensor
5 0 1 Temperature Night 32 - 86 °F 61
5 0 2 Fixed Temperature
86 - 179 °F 179 Parameter 5.2.0 = 1
68 - 122 °F 120 Parameter 5.2.0 = 0
5 0 3 Zone Freeze Protection Temperature 36 - 59 °F 41
Only applicable when using an
NTI room sensor - Changes all
zones
5 1 SUMMER/WINTER CHANGEOVER
5 1 0 S/W function activation 0 = OFF, 1 = ON 0
5 1 1 S/W temperature threshold 50 - 86 °F 68
5 1 2 S/W delay time 0 - 300 minutes 60
5 2 ZONE 2 SETTINGS
5 2 0 Temperature Range
0 = 68 - 122°F (low temperature)
1 = 86 - 179°F (high temperature)
1
Part 9 - Controls