4.6 Troubleshooting
E.438 – Abnormal circulation pump
о Error description:
Incongruity between Pump activation signal and Flow Sensor reading.
о Potential causes:
Air-lock
During commissioning, the rst Central Heat call may introduce air into the pump, which can overwhelm
the impeller and induce air-lock.
Faulty Flow Sensor or Pump
It is possible that the pump is failing to generate any ow, or that the sensor is failing to read it.
о Troubleshooting:
If air-lock is suspected (when error appears during Central Heating):
Ensure that the air eliminator on top of the pump housing is open.
Flood the pump chamber by opening the valve between it and the Buer Tank (set it to 'INT')
Press Reset button (bottom left) to clear the error code and resume Central Heating (if call still active).
Once the pump resumes operation, air should begin escaping from the eliminator.
Slowly close the valve by the valve by setting it back to 'EXT'. Air should continue to escape.
If E.438 re-appears, repeat this procedure. If the air-lock does not clear after 3 attempts, check inlet
water supply (and pressure), and attempt a Central Heat call with a simultaneous DHW draw (~ 2 GPM).
Otherwise:
Check Flow Sensor:
Get back to Stand-by mode (i.e. stop heating (‘W’) call).
Apply a DHW draw and observe the ow sensors output.
Press Info button (middle left), then [ ] to see the current ow rate (GPM).
If readout corresponds to expected ow rate value (based on visible water ow at the xture), we can
eliminate the Flow Sensor as the root of the error.
Check that brass isolation valve is open
Make sure the black plastic handle is parallel to the valve body and piping
Perform a Pump Test
From Stand-by, press and hold Diagnostics button (top left) for 5 seconds to enter Test mode
Press Info button to enter Test menu, and use [ + ] and [ ] buttons to scroll to “Pump.
Press Info button to start the test (5-10 seconds on/o cycles for 1 minute)
Observe display readout it should cycle between “On / “O and “_ . _” GPM
If these steps fail to resolve the error, contact NTI Technical Support for further assistance.