24/02/2020 21 / 24 923650001_09_008.doc
“TIME SETTING” set the time of the panel
SELECT LANGUAGE” choose language between GREEK and ENGLISH
“BUZZER SETTINGS” set buzzer on/off
ANNUAL CHECK WARNING” enable/disable the annual check warning
“MENU MANUFACTURER” you need the code of the manufacturer to access this
menu
4.2. Function test menu
The menu “SET FUNCTION TEST” has the options below:
SET FUNCTION TEST TIME INTERVAL
DAILY
EVERY OTHER DAY
EVERY SUNDAY
HOUR XX:XX
EVERY MONDAY
EVERY TUESDAY
EVERY WENSDAY
EVERY THURSDAY
EVERY FRIDAY
EVERY SATURDAY
Figure 4-16
First you choose how often the function test takes place, from daily to once a week and then you
choose the exact time.
At the function test the panel will send a command to every luminaire to make a function test. After the
test all faults will be displayed at the panel.
4.3. Capacity test menu
SET CAPACITY TEST
HOUR XX:XXDATE XX/XX
CHOOSE TEST 1..2 ACTIVE YES/NO
Figure 4-17
At the figure above you set when the capacity tests take place in a year. In every year the maximum
number of capacity test is 2.
It is recommended that the panel takes two capacity tests per year, once every 6 months.
A technician can start a capacity test by selecting the option “MAKE A CAPACITY TEST”.