32
Installation
,
O
p
eration and Maintenance Manual ManRE20en Rev.06/2022
OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468
Level 1 Level 2 Range
Initial factory setting
Input Configuration
[IN CFG]
Characterization [CHAR]
Linear, Quick Open,
Equal Percent, User Set
5point, User Set 21point
[LIN, QO, EQ, U5, U21]
LIN
User Set Characterization 5p
[USER 5P]
0%, 25%, 50%, 75%, 100%
User Set Characterization 21p
[USER 21P]
0%, 5%, 10%, … 95%,
100%
Tight Shut Open [TSHUT OP] 0.1 ~ 100 [%] 100.0 %
Tight Shut Close [TSHUT CL] 0.1 ~ 100 [%] 0.3 %
Output Configuration
[OUT CFG]
Position Transmitter Direction
[PTM]
[NORM, REVS] NORM
Position Transmitter Zero
[PTM ZERO]
0 ~ 100.00 [%]
Position Transmitter End
[PTM ENd]
0 ~ 100.00 [%]
Back Calculation [bAKCAL] [oFF, on] oFF
Device Configuration
[dEV CFG]
Action Change [ACT]
[dIR, REVS] REVS
Linear Interpolation [ITP] [oFF, on]
on with Linear
oFF with Rotary
Write Protect [W] [UNLOCK, LOCK] UNLOCK
View Mode [VI] [NORM, REVS] NORM
Factory Reset [dEFAULT]
Self-Test [SELFTEST]
Diagnosis [dIAGNO]
Device Status [dS] GOOd, Refer to 8.14
Status and Alarm Code.
GOOd
Reset Alarm Status [RST ALRM]
View Event Log [EVT LOG]
RECORD 0 - 19 1
Information [INFO] Model Name [RE20*]
Firmware Version [SOFT VER]
Download Date
*.*.**
YYYYMMDD
Program current version
Program input date
Run Time [RT] *.**
RT *d
Upward Stroke Time [FULL OP]
**.**
Downward Stroke Time
[FULL CL]
**.**
Position Sensor Type [PSNT]
PTN, NCS
Absolute Position in Angle
[AbS ANGL]
***.* °

Table of Contents