51
Installation
,
O
p
eration and Maintenance Manual ManRE20en Rev.06/2022
OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468
3 seconds
<UP>/<DOWN>
Press <UP> or
<DOWN> button
if the above is not
displayed.
Adjusting zero
point.
Press <UP> or
<DOWN> button
if the above is not
displayed.
The actuator
moves to zero
point.
<UP>/<DOWN>
<ESC>
<DOWN>
Fit the feedback
signal to 4mA..
<UP>/<DOWN>
<ESC>
3 times
Adjusting end point.
The actuator
moves to end
point.
Fit the feedback
signal to 20mA..
8.10.3 Back Calculation (bACKCAL oFF / on)
This function recalculates the output "RUN AP" value changed by the flow characteristics setting
mode to display it linearly proportional to actual input current. For example, if the flow characteristic
mode is set from "LIN" to "EQ", when an input current value of 8 mA (25 %) is applied, the target
position is changed to 6.25 % and "RUN AP" is displayed as 6.25 % after the move. If you change
the bACKCAL from OFF to ON, the "RUN AP" is displayed as 25 %.
3 seconds
Press <UP> or
<DOWN> button
if the above is not
displayed.
Press <UP> or
<DOWN> button
if the above is not
displayed.
<UP>/<DOWN>
<ESC>
3 times