8.5 Configuration and Operation
The Table below shows the eight Configuration/Operation menus, each submenu, ranges for each
parameter, and initial factory settings. The words shown in [ ] for each menu represent the
abbreviations of each word displayed when operating the LCD screen.
Level 1 Level 2 Range
Initial factory setting
Calibration [CALIb]
Acting Type [SINGLE, dOUbLE]
Auto Calibration 1 [AUTO 1]
Auto Calibration 2 [AUTO 2]
Travel Zero [TVL ZERO]
Travel End [TVL ENd]
Manual Operation
[MAN OPER]
Manual Operation by Set Position
[MAN SP]
Manual Operation by Manipulator
Value [MAN MV]
Control Parameters
[CTL PARM]
Dead Band [dEAdbANd] 0.1 ~ 10.0 [%] 0.3 %
Proportional Gain, Upward [KP UP] 0.1 ~ 50.0 1
Proportional Gain, Downward
[KP dN]
0.1 ~ 50.0 1
Integral Gain, Upward [TI UP] 0.1 ~ 50.0 1
Integral Gain, Downward [TI dN] 0.1 ~ 50.0 1
Differential Gain, Upward [Kd UP] 0.1 ~ 50.0 1
Differential Gain, Downward [Kd dN] 0.1 ~ 50.0 1
Auto Dead Band Mode [AUTO db] oFF, [0%] oFF
Performance Mode [PER]
Stable, Normal, Fast
[STbL, NORM, FAST]
NORM
Input Configuration
[IN CFG]
Signal Direction [SIG]
Normal, Reverse
[NORM, REVS]
NORM
Split Range Mode [SPLIT]
4 ~ 20, 4 ~ 12, 12 ~ 20,
Custom
[4.20, 4.12, 12.20, CSt]
4.20
Custom Split Range Zero
[CST ZERO]
4 ~ 20.0[mA] 4mA
Custom Split Range End
[CST ENd]
4 ~ 20.0[mA] 20mA