44
Installation
,
O
p
eration and Maintenance Manual ManRE20en Rev.06/2022
OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468
8.9.4 Custom Split Range End (CST ENd)
It is used to set the current corresponding to the endpoint when the valve position of 0 to 100% is
controlled by the user-set CUSTOM. For example, if the valve is controlled by 4-18 mA instead of 4-
20 mA, CST END is 18 mA. However, the difference of the current between the origin point and the
endpoint must be greater than 4 mA.
3 seconds
Press <UP> or
<DOWN> button
if the above is not
displayed.
Press <UP> or
<DOWN> button
if the above is not
displayed.
<UP>/<DOWN>
<ESC>
3 times
This function is activated by saving the Split Range Mode (SPLIT) of above Section 8.9.2 as “CSt”.
8.9.5 Valve Flow Characterization Curves (CHAR)
The flow characteristic curve of valve is available by
selecting one of the following: Linear(LIN), Quick Open(QO),
Equal Percentage(EQ), User Set Characterization 5 Points (U5),
User Set Characterization 21 Points(U21).