6
Installation
O
eration and Maintenance Manual ManRE20en Rev.06/2022
OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468
2. Product Description
2.1 General
RE20 Smart Valve Positioner accurately controls valve stroke in response to an input signal of
4~20mA from the controller. Built-in micro-processor optimizes the positioner’s performance and
provides unique functions such as Auto-Calibration, PID Control.
2.2 Main Features and Functions
LCD display enables users to monitor the positioner status.
User will easily understand the method of using 4 buttons because it work same in all versions of
firmware interfaces.
When unexpected situation like momentary blackout happens, our positioner boot-time only take
0.5 second and this can minimize the travel of valve which consequentially increase the safety of
system.
Positioner operates normally even there are sudden changes in supply pressure and / or high
vibration environment.
The method of Auto Calibration is very simple.
As an advantage of having very low air consumption, It could greatly reduce operating costs in
large-scale plants.
It is compatible with most of controllers.
Orifices can be installed even in the field to minimize the hunting occurrence and optimize
operating conditions.
Valve system becomes more stable by outputting analog feedback signal.
Different valve characteristics can be adjusted – Linear, Quick Open, Equal Percentage, and
User Set which user can make 5 or 21 points characterizations.
Tight Shut – Close and Shut - Open can be set.
PID parameters can be adjusted in the field without any additional communicator.
Split range 4~12mA or 12~20mA can be set.
Operating temperature for positioners is -30 ~ 85℃ (Please check certified explosion proof
temperature in case of Ambient temperature)
Hand calibration function can set Zero point or End point manually.
It has IP66 protection grade.
Polyester powder coating resists the corrosion process.
Maintenance of the positioner is easy because of modularized inner structure.