eration and Maintenance Manual ManRE20en Rev.06/2022
OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468
8.9.6 User Set Characterization 5 Points (U5)
A total of 5 target positions are set every 4 mA intervals. When shipped from the factory, the initial
positions are P0 (4mA, 0%), P1 (8mA, 25%), P2 (12mA, 50%), P3 (16mA, 75%), and P4 (20mA,
100%). User can change all 5 points or only change partially and exit the menu by pressing <ESC>
button.
3 seconds
Press <UP> or
<DOWN> button
if the above is not
displayed.
Press <UP> or
<DOWN> button
if the above is not
displayed.
<UP>/<DOWN>
or
<UP>/<DOWN>
or
<UP>/<DOWN>
or
<UP>/<DOWN>
or
<UP>/<DOWN>
or
To automatically
move after
several seconds.
<ESC>
2 times
This function is activated by saving the Valve Flow Characterization Curves (CHAR) of above Section
8.9.5 as “U5”.