Series User’s Guide
Reference Section: Initialization Mode (INIt)
Navigate to the correct setting. Settings include the following:
• bUS.F – Specify RS232 or RS485 serial communications
• bAUd – Baud rate (transmission rate)
• PRty – Parity (used for transmission error checking)
• dAtA – Number of bits per data point
• StoP – Number of stop bits between data points
Select the desired setting.
4.4.3.1 Serial Bus Format (INIt > CoMM > SER > C.PAR >
bUS.F)
Select the Bus Format (bUS.F) parameter.
Navigate to the desired setting. Settings include the following:
• 232C – Allows one-to-one serial communications (factory default)
• 485 – Allows multiple devices to operate on a single pair of wires
Select the indicated option.
4.4.3.2 Baud Rate (INIt > CoMM > SER > C.PAR > bAUd)
Select the Baud Rate (bAUd) parameter. The device being communicated to
determines how fast you can set the Baud Rate.
Navigate to the desired setting for Baud rate (bits per second):
• 19.2 – 19,200 Baud (factory default)
• 9600 – 9,600 Baud
• 4800 – 4,800 Baud
• 2400 – 2,400 Baud
• 1200 – 1,200 Baud
• 57.6 – 57,600 Baud
• 115.2 – 115,200 Baud
Select the indicated option.
4.4.3.3 Parity (INIt > CoMM > SER > C.PAR > PRty)
Select the Parity (PRty) parameter.
Navigate to the desired setting. Settings include the following:
• odd – Odd parity used to verify communications (factory default)
• EVEN – Even parity used to verify communications
• NoNE – Parity is not used to verify communications
Select the indicated option.
4.4.3.4 Data Bits (INIt > CoMM > SER > C.PAR > dAtA)
Select the number of Data Bits (dAtA).
Omega Engineering | www.omega.com