List of Parameters
13
Param-
eter
No.
Name Description Setting
range
Unit of
setting
(see note)
Default
setting
Changes
during op-
eration
Reference
page
n59 Overtorque
detection function
selection
Used to enable or disable overtorque detection and
select the processing method after overtorque
detection.
0 to 4 1 0 No 19
n60 Overtorque
detection level
Used to set overtorque detection level. 30 to 200 1% 160 No 19
n61 Overtorque
detection time
Used to set the detection time of overtorque. 0.1 to 10.0 0.1 s 0.1 No 19
n62 UP/DOWN
command frequency
memory
Used to store the adjusted frequency reference with the
UP/DOWN function.
0, 1 1 0 No 20
n63 Torque
compensation gain
Used to set the gain of the torque compensation
function.
0.0 to 2.5 0.1 1.0 Yes 21
n64 Motor rated slip Used to set the rated slip value of the motor in use. 0.0 to 20.0 0.1 Hz Varies
with the
capacity.
Yes 21
n65 Motor no-load
current
Used to set the no-load current of the motor in use
based on the rated motor current as 100%.
0 to 99 1% Varies
with the
capacity.
No 21
n66 Slip compensation
gain
Used to set the gain of the slip compensation function. 0.0 to 2.5 0.1 0.0 Yes 21
n67 Slip compensation
time constant
Used for the response speed of the slip compensation
function.
0.0 to 25.5 0.1 s 2.0 No 21
n68 to
n74
OMRON’s control
reference use
Do not change the set value. --- --- --- --- ---
n75 Low-speed carrier
frequency reduction
selection
Used to select a function to reduce the carrier
frequency when Inverter is at low speed.
0.1 1 0 No ---
n76
OMRON’s control
f
Do not change the set value. --- --- --- --- ---
n77
OO
reference use
g
n78 Error log Used to display the latest error recorded.
Display
Note “– – –” will be displayed if no error has been re-
corded.
Note This parameter is monitored only.
--- --- --- --- ---
n79 Software number Used to display the software number of the Inverter for
OMRON’s control reference use.
Note This parameter is monitored only.
--- --- --- --- ---
Note: Values longer than 3 digits are rounded up to the next unit multiple.