286
PLC Setup Section 7-1
Serial Gateway Settings
Communications Setting
Mode: Communications Mode
Format: Data Bits
Format: Stop Bits
Address in
Programming
Console
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
144 15 0: Default (stan-
dard)*
1: PLC Setup (cus-
tom)
*The default settings are for a baud rate of
9,600 bps.
A61901
(Peripheral
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
144 8 to 11 9: Serial Gateway
Default: 0
This setting determines whether the com-
munications mode for the peripheral port.
The peripheral bus mode is used for all Pro-
gramming Devices except for Programming
Consoles.
A61901
(Peripheral
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
144 3 0: 7 bits
1: 8 bits
Default: 0
These settings are valid when the Periph-
eral Port Settings Selection is set to 1: PLC
Setup.
A61901
(Peripheral
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
144 2 0: 2 bits
1: 1 bit
Default: 0
These settings are valid when the Periph-
eral Port Settings Selection is set to 1: PLC
Setup.
A61901
(Peripheral
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)