A - 11
Appendices
NX-series EtherNet/IP Coupler Unit User’s Manual (W536)
A-1 Supported CIP Objects
A
A-1-3 NX Configuration Object (Class ID: 74 Hex)
Format for Normal Response
Format for Error Response
CIP error code
Switch Parameter Write Mode (Service Code: 37 Hex)
The request format, format for normal responses, format for error responses, and CIP error codes
for the Switch parameter write mode object are given below.
Request Format
Unit No Unit number UINT 0000: Communications Coupler Unit
0001 to 003F: NX Unit
0040 or higher: Not supported.
Parameter name Description
Data
type
Value
(hex)
Reply Service Reply to Save parameter service USINT B6
Reserved Reserved USINT 00
General Status Code that indicates normal USINT 00
Size of Additional Status Size of Additional status USINT 00
Parameter name Description
Data
type
Value (hex)
Reply Service Reply to Save parameter service USINT B6
Reserved Reserved USINT 00
General Status Current error code defined by CIP USINT Current error code
Size of Additional Status Size of Additional status USINT
00
*1
*1. If the general status code in the response code is 0x1F (Vendor specific error), the value is 0x01.
Additional status Additional status UINT
Additional status
*2
*2. This is stored only when the value of Size of Additional Status is 0x01.
General status code (hex)
Error code
*1
*1. Refer to General Status Code on page A-30 for error descriptions.
02 Resource unavailable
13 Not enough data
15 Too much data
19 Store operation failure
1F Vendor specific error
20 Invalid parameter
Parameter name Description Data type Value (hex)
Service Service code USINT 37
Request Path Size Request path size USINT 02
Request Path Request path Padded EPATH 20742401
Unit No Unit number UINT 0000: All Units in the Slave Terminal
0001 to 003F: NX Unit
0040 or higher: Not supported.
Parameter name Description Data type Value (hex)