7
EtherNet/IP Connection Procedure
53
14
Select Display - Binary from the
View Menu.
15
Enter 10000 in the Start Address
Field of the D Window.
Check that the start address
changes to D10000.
Select the bit 0 value of D10000 in
the D Window.
16
Click On.
The bit 0 value of D10000 changes
to 1.
*D10000 Bit 0: Control command
execution
17
Enter 10100 in the Start Address
Field of the D Window.
Check that the start address
changes to D10100 and that the bit
0 value of D10100 is 1.
*D10100 Bit 0: Control command
completion
18
Select Display - Hexadecimal from
the View Menu.
19
Check that the values of D10106
and D10107 show the command
values set in steps 10 and 11,
respectively.
*D10106, D10107: Command code
echo