355
Serial Communications Section 6-1
Related Auxiliary Area Flags for Serial Port 1
Note In the same way as for the existing 1:N NT Link, the status (communicating/
not communicating) of PTs in Serial PLC Links can be checked from the Poll-
ing Unit (CPU Unit) by reading the Serial Port 1 Communicating with PT Flag
(A394 bits 00 to 07 for unit numbers 0 to 7).
Name Address Details Read/write Refresh timing
Serial Port 1
Communicating
with PT Flags
(See note.)
A394.00 to
A394.07
When serial port 1 is
being used in NT link
mode, the bit correspond-
ing to the Unit performing
communications will be
ON. Bits 00 to 07 corre-
spond to unit numbers 0
to 7, respectively.
ON: Communicating
OFF: Not communicating
Read Cleared when power is turned ON.
Turns ON the bit corresponding to the
unit number of the PT/Polled Unit that is
communicating via serial port 1 in NT link
mode or Serial PLC Link mode.
Bits 00 to 07 correspond to unit numbers
0 to 7, respectively.
Serial Port 1
Restart Bit
A526.01 Turn ON this bit to restart
serial port 1.
Read/write Cleared when power is turned ON.
Turn ON to restart serial port 1, (except
when communicating in peripheral bus
mode).
Note The bit is automatically turned OFF
by the system when restart process-
ing has been completed.
Serial Port 1
Error Flags
A528.08 to
A528.15
When an error occurs at
serial port 1, the corre-
sponding error bit is
turned ON.
Bit 08: Not used.
Bit 09: Not used.
Bit 10: Parity error
Bit 11: Framing error
Bit 12: Overrun error
Bit 13: Timeout error
Bit 14: Not used.
Bit 15: Not used.
Read/write Cleared when power is turned ON.
When an error occurs at serial port 1, the
corresponding error bit is turned ON.
The flag is automatically turned OFF by
the system when serial port 1 is
restarted.
In NT link mode, only bit 05 (timeout
error) is enabled.
In Serial PLC Link mode, only the following
bits are enabled.
Errors at the Polling Unit:
Bit 05: Timeout error
Errors at Polled Units:
Bit 05: Timeout error
Bit 04: Overrun error
Bit 03: Framing error
Note If the error occurred in Serial PLC link
mode, the console will retry before
communication establish. Rehabilita-
tion of the communications is no need
for port restart. If user eliminates
error, the communication will auto-
matically establish between console
and servo.
However, error flag will be saved as
the record. If you want to clear the
error flag, please restart port.
Serial Port 1 Set-
tings Changed
Flag
A619.01 Turns ON when the com-
munications conditions of
serial port 1 are being
changed.
ON: Changed
OFF: No change
Read/write Cleared when power is turned ON.
Turns ON while communications condi-
tions settings for serial port 1 are being
changed.
Turns ON when the CHANGE SERIAL
PORT SETUP instruction (STUP(237)) is
executed.
Turns OFF when the changes to settings
are completed.