Omron CP1H-X40D - Other Errors

Omron CP1H-X40D
810 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
616
Troubleshooting Section 11-2
11-2-6 Other Errors
Communications Errors
CPU Unit Indicators
POWER Lit
RUN Lit
ERR/ALM ---
INH ---
BKUP Not lit
PRPHL ---
Seven-segment
display
Probable cause and possible remedy
None An error has occurred in the communications between the periph-
eral port and connected device. Confirm that the peripheral port
settings in the PLC Setup are correct.
An error has occurred in the communications between the RS-
232C port and connected device. Confirm that the RS-232C port
settings in the PLC Setup are correct. Check the cable wiring. If a
host computer is connected, check the serial port settings and
program in the host computer.
An error will be occurred if the cycle time is too long. Modify the
CX-Programmer's response monitoring time longer according to
the following method.
Start the CX-Programmer. Select Change Model from the PLC
Menu. The Change PLC Dialog Box will be displayed. Click the
Settings Button on the right side of Network Type. The Network
Settings [USB] Dialog Box will be displayed. Click the Network
Tab and increase the value in Response Timeout(s).
POWER RUN
INH
PRPHL BKUP
ERR/ALM