Analog Input Units Section 7-2
0 to 20 mA Inputs
When the resolution is 1/6,000, the 0 to 20 mA range corresponds to hexa-
decimal values 0000 to 1770 (0 to 6,000). The range of data that can be con-
verted is FED4 to 189C hex (–300 to 6,300).
A negative current is expressed as two’s complement.
When the resolution is 1/12,000, the 0 to 20 mA range corresponds to hexa-
decimal values 0000 to 2EE0 (0 to 12,000). The entire data range is FDA8 to
3138 hex (–600 to 12,600).
A negative current is expressed as a two’s complement.
4 to 20 mA Inputs
When the resolution is 1/6,000, the 4 to 20 mA range corresponds to hexa-
decimal values 0000 to 1770 (0 to 6,000). The range of data that can be con-
verted is FED4 to 189C hex (–300 to 6,300).
Current in the range of 3.2 to 4 mA is expressed as two’s complement.
If an input is below the range (i.e., less than 3.2 mA), the open-circuit detec-
tion function is activated and the data becomes 8,000.
When the resolution is 1/12,000, the 4 to 20mA range corresponds to hexa-
decimal values 0000 to 2EE0 (0 to 12,000). The entire data range is FDA8 to
3138 hex (–600 to 12,600).
Current in the range of 3.2 to 4 mA is expressed as two’s complement.
If an input is below the range (i.e., less than 3.2 mA), the open-circuit detec-
tion function is activated and the data becomes 8,000.
0 mA 20 mA
21 mA
1 mA
Converted data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
FED4 (300)
0 mA 20 mA
21 mA
1 mA
FDA8 (600)
3138 (12600)
2EE0 (12000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
Converted data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
FED4 (300)
4 mA 20 mA
20.8 mA
3.2 mA
0 mA