417
Analog I/O Units Section 7-4
Analog Input Signal
Ranges
10 to 10 V
The 10 to 10 V range corresponds to the hexadecimal values F448 to 0BB8
(3000 to 3000). The entire data range is F31C to 0CE4 (3300 to 3300).
A negative voltage is expressed as a two’s complement.
0 to 10 V
The 0 to 10 V range corresponds to the hexadecimal values 0000 to 1770 (0
to 6000). The entire data range is FED4 to 189C (300 to 6300). A negative
voltage is expressed as a two’s complement.
0 to 5 V
The 0 to 5 V range corresponds to the hexadecimal values 0000 to 1770 (0 to
6000). The entire data range is FED4 to 189C (300 to 6300). A negative volt-
age is expressed as a two’s complement.
0 V 10 V
11 V
11V
10V
F448 (3000)
F31C (3300)
0CE4 (3300)
0BB8 (3000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
0 V 10 V
10.5 V
0.5 V
FED4 (300)
189C (6300)
1770 (6000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
0 V 5 V
5.25 V
0.25 V
FED4 (300)
189C (6300)
1770 (6000)
0000 (0)
Converted Data
Hexadecimal (Decimal)