433
Analog I/O Units Section 7-4
Analog Output Signal
Ranges
10 to 10 V
The hexadecimal values E890 to 1770 (6000 to 6000) correspond to an ana-
log voltage range of 10 to 10 V. The entire output range is 11 to 11 V. Spec-
ify a negative voltage as a two’s complement.
0 to 10 V
The hexadecimal values 0000 to 2EE0 (0 to 12000) correspond to an analog
voltage range of 0 to 10 V. The entire output range is 0.5 to 10.5 V. Specify a
negative voltage as a two’s complement.
1 to 5 V
The hexadecimal values 0000 to 2EE0 (0 to 12000) correspond to an analog
voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V.
0 V
10 V
11 V
11 V
10 V
E890
(6000)
E638
(6600)
19C8
(6600)
1770
(6000)
0000 (0)
8000
7FFF
Conversion Data
Hexadecimal (Decimal)
0 V
10 V
10.5 V
0.5 V
FDA8
(600)
3138
(12600)
2EE0
(12000)
0000 (0)
8000
7FFF
Conversion Data
Hexadecimal (Decimal)
1 V
5 V
5.2 V
0.8 V
3138
(12600)
2EE0
(12000)
0 V
7FFFFDA8
(600)
8000
Conversion Data
Hexadecimal (Decimal)

Table of Contents