Temperature Sensor Units Section 7-5
Main Specifications
Note Accuracy for a K-type sensor at −100°C or less is ±4°C ±1 digit max.
Using Temperature Sensor Units
Connecting Temperature
Sensor Units
A maximum of three CP1W-TS002 and CP1W-TS102 Temperature Sensor
Units can be connected, because each unit is allocated four words.
Item CP1W-TS001 CP1W-TS002 CP1W-TS101 CP1W-TS102
Temperature sensors Thermocouples Platinum resistance thermometer
Switchable between K and J, but same type
must be used for all inputs.
Switchable between Pt100 and JPt100, but
same type must be used for all inputs.
Number of inputs2424
Allocated input words2424
Max. number of Units7373
Accuracy (The larger of ±0.5% of converted value or
±2°C) ±1 digit max. (See note.)
(The larger of ±0.5% of converted value or
±1°C) ±1 digit max.
Conversion time 250 ms for 2 or 4 input points
Converted temperature data 16-bit binary data (4-digit hexadecimal)
Isolation Photocouplers between all temperature input signals
Current consumption 5 VDC: 40 mA max., 24 VDC: 59 mA max. 5 VDC: 54 mA max., 24 VDC: 73 mA max.
Set the temperature ranges.
Connect the temperature
sensors.
Connect the Temperature
Sensor Units.
Operation in the ladder
program.
• Set the temperature unit, 2-decimal-place Mode
if required, and set the temperature input range.
• Connect the Temperature Sensor Units to the
CPU Unit.
• Connect temperature sensors.
• Read temperature data stored in the input word.
CP1H CPU Unit
IN
00
CH
CH
02 04 06 08 10
OUT
01COM 03 050709 11
COM COM COM 03COM06
00 01 02 04 05 07
00 01 02 03 04 05 06
07
08 09 10 11
20EDR1
CH
00 01 02 03 04 05 06 07
NC
NC
NC
CH
EXP
IN
00 02
01COM 03
COM 0507
04 06
CH
00 01 02 03
08 09 10 11
8ED
EXP
CP1W-20EDR1
Expansion I/O Unit
CP1W-8ED
Expansion I/O Unit
CP1W-TS001/TS101