473
Temperature Sensor Units Section 7-5
Programming Example
The temperature data of CP1W-TS004 (12 inputs, input type is J type and
temperature unit is °C) is stored in D0 to D11.
When it occurs open-circuit alarm, W10.00~W10.11 is ON.
Temperature Data Storage Address
Input word Read command
CIO n+1
Temperature data
storage address
Open-circuit alarm
Input 0 #9901 D0 W0.00
Input 1 #9902 D1 W0.01
Input 2 #9903 D2 W0.02
Input 3 #9904 D3 W0.03
Input 4 #9905 D4 W0.04
Input 5 #9906 D5 W0.05
Input 6 #9907 D6 W0.06
Input 7 #9908 D7 W0.07
Input 8 #9909 D8 W0.08
Input 9 #990A D9 W0.09
Input 10 #990B D10 W0.10
Input 11 #990C D11 W0.11
CIO 102
CP1H
Input word
addresses
Input range
J: SW1 OFF
Temperature unit
˚C: SW2 ON
Output word
addresses
CIO 0
CIO 1
CIO 100
CIO 101
CIO 2
CIO 3
CP1W-TS004
Temperature Sensor Unit