558
Installation and Initial Setup Section 9-8
9-8-2 Installation and Removing
The following processing explains how to install and remove an Ethernet
Option Board.
!Caution Always turn OFF the power supply to the CPU unit and wait until all the oper-
ation indicators go out before installing or removing the Ethernet Option
Board.
Installation
1,2,3... 1. Press the up/down lock-levers on both sides of the Option Board slot cover
at the same time to unlock the cover, and then pull the cover out.
2. Check the alignment to make the corner cut of the Ethernet Option Board
fit in the Option Board slot, and firmly press the Ethernet Option Board in
until it snaps into place.
Note If two CP1W-CIF41 (unit version 1.0) Ethernet Option Boards are
mounted on the CP1L/CP1H PLC, the CP1W-CIF41 mounted on Op-
tion Board slot1 (left side) will run in abnormal status and ERR indicator
will be ON. If the ladder program operates the with CP1W-CIF41 fatal
error, the PLC will generate the non-fatal error.
Ethernet Option Board
BackFront
Corner Cut
Operation indicators
Option Board slot 1
Option Board slot 2

Table of Contents

Related product manuals