Specifications Section 2-2
Note (1) The above values are for a cold start at room temperature for an AC pow-
er supply, and for a cold start for a DC power supply.
• A thermistor (with low-temperature current suppression characteris-
tics) is used in the inrush current control circuitry for the AC power
supply. The thermistor will not be sufficiently cooled if the ambient
temperature is high or if a hot start is performed when the power sup-
ply has been OFF for only a short time, so in those cases the inrush
current values may be higher (as much as two times higher) than
those shown above.
• A capacitor delay circuit is used in the inrush current control circuitry
for the DC power supply. The capacitor will not be charged if a hot
start is performed when the power supply has been OFF for only a
short time, so in those cases the inrush current values may be higher
(as much as two times higher) than those shown above.
• Always allow for this when selecting fuses and breakers for external
circuits.
(2) General specification of Expansion I/O Units and Expansion Units will be
the same criteria with CPU Units.
Characteristics
Dielectric strength 2,300 VAC 50/60 Hz for 1 min between the
external AC and GR terminals, leakage current:
5 mA max.
No insulation between primary and secondary
DC power supplies.
Noise resistance Conforms to IEC 61000-4-4 2 kV (power supply line)
Vibration resistance
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s
2
in X, Y, and Z directions for
80 minutes each (time coefficient of 8 minutes × coefficient factor of 10 = total time of 80 minutes)
Shock resistance
147 m/s
2
three times each in X, Y, and Z directions
Ambient operating
temperature
0 to 55°C
Ambient humidity 10% to 90% (with no condensation)
Atmosphere No corrosive gas.
Ambient storage
temperature
−20 to 75°C (excluding battery)
Terminal screw size M3
Power interrupt time 10 ms min. 2 ms min.
Weight 740 g max. 590 g max. 560 g max.
Power supply
classification
AC power supply DC power supply
Model numbers • XA CPU Units
CP1H-XA40DR-A
• X CPU Units
CP1H-X40DR-A
• XA CPU Units
CP1H-XA40DT-D
CP1H-XA40DT1-D
• X CPU Units
CP1H-X40DT-D
CP1H-X40DT1-D
• Y CPU Units
CP1H-Y20DT-D
Type X CPU Units XA CPU Units Y CPU Units
Model CP1H-X40DR-A
CP1H-X40DT-D
CP1H-X40DT1-D
CP1H-XA40DR-A
CP1H-XA40DT-D
CP1H-XA40DT1-D
CP1H-Y20DT-D
Program capacity 20 Ksteps
Control method Stored program method
I/O control method Cyclic scan with immediate refreshing
Program language Ladder diagram