5-5SectionTroubleshooting Flowcharts
135
Fatal Error Check
Identify the error, eliminate
its cause, and clear the
error.
Follow the Memory Error
Check flowchart if a
memory error has occurred.
Is the ERR/ALM
indicator lit?
Determine the cause
of the error with a
Programming Device.
End
RUN indicator not lit.
Replace the CPU
Unit.
Is PC mode displayed
on Programming
Device?
Turn the power
supply OFF, and
then ON again.
Switch to RUN or
MONITOR mode.
No
Yes
Is a fatal error
displayed?
Is PC mode displayed on
Programming Device?
No
Yes
Yes
No
Is the RUN
indicator lit?
No
Yes
Yes
No

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CPM2A - 11-2005 and is the answer not in the manual?

Omron CPM2A - 11-2005 Specifications

General IconGeneral
CategoryController
ManufacturerOmron
Output TypeRelay
Input Voltage24 VDC
Supply Voltage100 to 240 VAC
Timer/Counter256
Communication PortRS-232
Operating Temperature0 to 55°C
Humidity10% to 90% RH (with no condensation)
Program Capacity2048 Steps