4 Basic Operation
4 - 52
E5@C-T Digital Temperature Controllers User’s Manual (H185)
z All PID 100% AT and All PID 40% AT
For details on All PID 100% AT and All PID 40% AT, refer to 5-14 Determining PID Constants for
PID Sets (Autotuning for All PID Sets).
The 100% autotuning is executed.
Operating Procedure
1
Press the M Key several times in the Adjustment Level to dis-
play at (AT Execute/Cancel).
Adjustment Level
2
Press the U or D Key to select at-2 (100% AT execute).
* The TUNE indicator will light during autotuning.
3
When AT ends, the AT Execute/Cancel parameter is set to off.
Adjustment Level
4-9-2 RT (Robust Tuning) (Used for Autotuning)
When autotuning is executed with RT selected, PID constants are
automatically set that make it hard for control performance to degenerate even
when control object characteristics change.
RT can be set in the Advanced Function Setting Level when PID control has
been set.
The RT mode cannot be selected while an analog input is set.
Selecting the RT mode in the following cases will help to prevent hunting from
occurring.
When the set temperature is not constant and is changed in a wide range
When there are large variations in ambient temperatures due to factors such
as seasonal changes or differences between day and night temperatures
When there are large variations in ambient wind conditions and air flow
When heater characteristics change depending on the temperature
When an actuator with disproportional I/O, such as a phase-control-type
power regulator, is used
When a rapidly heating heater is used
When the control object or sensor has much loss time
When hunting occurs in normal mode for any reason
* PID constants are initialized to the factory settings by switching to RT
mode.
* When the RT mode is selected, the Integral/Derivative Time Unit pa-
rameter changes to 0.1 s.
off
at
AT Execute/
Cancel
at-2
at
off
at
AT Execute/
Cancel
rt