5 Advanced Operations
5 - 56
E5@C-T Digital Temperature Controllers User’s Manual (H185)
z Related Parameters
Enabling Waiting and Setting a Wait Band
Enabling and Disabling Waiting with an Event Input
You can repeatedly execute the same program.
Setting program repetitions automatically restarts execution of the same program from segment 0
after the final segment is executed. You can set the number of program repetition to up to 9,999 rep-
etitions. Set the number of program repetitions in the Program Repetitions parameter (Program Set-
ting Level).
The number of executions will be one more than the specified number of program repetitions.
If the Program Repetitions parameter is changed to a smaller number during program operation, the
currently executing program will be executed to the end and then the program will stop.
z Related Parameters
You can specify the number of the next program to execute when execution of a program is completed.
When the last segment is executed, execution will move to segment 0 of the program specified in the
Program Link Destination parameter (Program Setting Level). Operation will be ended if the Program
Link Destination parameter is set to END.
If a program repeat operation is also set, the program link will start after the program repetition
operation has been completed.
If the current program number is specified in the Program Link Destination parameter, the program
will be repeated indefinitely.
After all programs have been executed, operation will be according to the setting for the Operation
End Operation parameter.
z Related Parameters
Parameter
name
Display Setting range Default Level
Wait Band wt-b
Temperature input: 0.1 to 999.9°C or °F,
Analog input: 0.01 to 99.99
off
Adjustment Level
Parameter
name
Display Setting range Default Level
Event Input
Assignment
eV-1
eV-2
eV-3
eV-4
eV-5
eV-6
wait: Wait Enable/Disable
Event Input
Assignment 1:
rr-1
Event Input
Assignment 2:
adv
Event Input
Assignment 3 to
6: none
Initial Setting
Level
5-15-5 Program Repetition
Parameter name Display Setting range Default Level
Program Repetitions rpt 0 to 9999 0 Program Setting Level
5-15-6 Program Links
Parameter name Display Setting range Default Level
Program Link Destination link end, 0 to 7end Program Setting Level