5 Advanced Operations
5 - 82
E5@C-T Digital Temperature Controllers User’s Manual (H185)
5-22 Logic Operations
The logic operation calculates the Controller status (alarms, run/reset, auto/manual, etc.) and the
external event input status as 1 or 0, and outputs the result to a work bit. The work bit status can be
output to auxiliary or control outputs, and operating status can be switched according to the work bit
status.
Work bit logic operation can be set from 1 to 8. Set them to No operation (Always OFF) (the default)
when the work bits are not to be used.
When logic operations are being used, a dot will be displayed between the first two digits on the No. 2
display of the Adjustment Level display
Note: The four numeric digits to identify the product code are displayed in the No. 2 display.
Logic operations are set using the CX-Thermo.
z Starting Logic Operations
There are two ways to start logic operations.
Select Logic Operation Editor from the CX-Thermo tree, and click the Start Button.
Select Logic Operation Editor from the CX-Thermo Options Menu.
5-22-1 The Logic Operation Function (CX-Thermo)
5-22-2 Using Logic Operations
123.4
l.adj
Dot displayed.
Adjustment level display
Adjustment Level