5 - 37
5 Advanced Operations
E5@C-T Digital Temperature Controllers User’s Manual (H185)
5-13 Using PID Sets
5
5-13-1 PID Sets
5-13 Using PID Sets
One set of all the parameters that are related to 2-PID control are called a PID set.
You can register up to eight PID sets.
There are the following two ways that you can specify PID sets.
Setting a Fixed PID Set
Using Automatic Selection of PID Sets by Zone
You can specify the PID set selection method for each program in the PID Set No. parameter in the
Program Setting Level.
The same PID sets are used for all programs.
z Related Parameters
Parameter Used to Select the PID Set to Edit
*If you press the U or D Key to change the PID set number, the current set number is no longer monitored.
PID Set Parameters
* = Set number 1 to 8
5-13-1 PID Sets
Parameter name Display Setting range Unit Default Level
Display PID Selection
(PID Set)
d.pid 1 to 8 ---
Currently
selected PID set*
PID Setting
Level
Parameter
name
Display Setting range Unit Default Level
PID *
Proportional
Band
*.p
Temperature input: 0.1 to 999.9 °C or °F 8.0
PID
Setting
Level
Analog input: 0.1 to 999.9 %FS 10.0
PID * Integral
Time
*1
*.i
Integral/Derivative
Time Unit of 1 s
Standard,
heating/cooling, or
close
position-proportional
control: 0 to 9999
Seconds 233
Floating
position-proportional
control: 1 to 9999
Integral/Derivative
Time Unit of 0.1 s
Standard,
heating/cooling, or
close
position-proportional
control: 0.0 to 999.9
Seconds 233.0
Floating
position-proportional
control: 0.1 to 999.9
PID * Derivative
Time
*1
*.d
Integral/Derivative
Time Unit of 1 s
0 to 9999
Seconds
40
Integral/Derivative
Time Unit of 0.1 s
0.0 to 999.9 40.0
PID *
Proportional
Band (Cooling)
*1
*.c-p Same as PID * Proportional Band.