5 Advanced Operations
5 - 8
E5@C-T Digital Temperature Controllers User’s Manual (H185)
* If the Controller is equipped with HB/HS alarm detection, it is set by default to ha (Heater Alarm).
The heating/cooling operation of the control outputs will switch when the Direct/Reverse
Operation parameter is set to direct operation.
When DRS (Invert Direct/Reverse Operation) is set for an Event Input Assignment 1 to 6
parameter, control will start with the opposite of the setting of the Direct/Reverse Operation
parameter when the event input turns ON. When the event input turns OFF, control will return to
operation according to the setting of the Direct/Reverse Operation parameter. For details on event
inputs and control combined with the Direct/Reverse Operation parameter, refer to Control by
Inverting Direct/Reverse Operation on page 5-13.
If heating/cooling control is selected, also set the Dead Band, Proportional Band (Cooling),
Integral Time (Cooling), Derivative Time (Cooling), and Heating/Cooling Tuning Method
parameters.
z Dead Band
For heating/cooling control, the dead band is set with the set point as its center. The dead band
width is the set value of the Dead Band parameter (Adjustment Level). Setting a negative value
produces an overlapping band.
If an overlapping band is set, the bumpless function may not operate when switching between
manual operation and automatic operation.
The default is 0.0 EU for Controllers with Temperature Inputs and 0.00% FS for Controllers with
Analog Inputs.
Auxiliary Output 2
Assignment
sub2 Alarm 2Alarm 2Alarm 2Alarm 2
Auxiliary Output 3
Assignment
sub3 Alarm 3Alarm 3Alarm 3Alarm 3
Auxiliary Output 4
Assignment
sub4 Alarm 4
Control output
(cooing)
Alarm 4 Alarm 4
Parameter name Display
Without control output 2 With control output 2
Standard Heating/cooling Standard Heating/cooling
0
PV
0
PV
Output
Dead band: Dead band
width = A positive value
Output
Heating
side
Cooling
side
Set point
Overlapping dead band: Dead band
width = A negative value
Heating
side
Cooling
side
Set point