EasyManua.ls Logo

Omron E5AC-T

Omron E5AC-T
438 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Advanced Operations
5 - 46
E5@C-T Digital Temperature Controllers User’s Manual (H185)
z Related Parameters
*1 These settings are not displayed if the PID Set Automatic Selection Data parameter is set to DV or the PID
Set No. parameter is not set to 0 (automatic selection).
*2 These settings are not displayed for heating/cooling control or floating position-proportional control.
*3 You cannot set the PID 8 Automatic Selection Range Upper Limit parameter. It will be the upper limit of the
input indication range.
Autotuning is not performed for PID sets that have the default settings.
If all PID sets have the default settings, 100% AT or 40% AT is performed.
All of the following conditions must be met to perform autotuning for all PID sets.
The must be no input errors.
The PID ON/OFF parameter must be set to PID or a position-proportional model must be used.
The Auto/Manual parameter must be set to automatic.
The PID Set Automatic Selection Data must be set to PV or SP. (Do not set it to DV.)
The PID Set No. parameter for the program to autotune must be set to 0 (automatic selection) and at
least one of the PID 1 to 7 Automatic Selection Range Upper Limits must be changed from the
default setting.
Parameter Display Setting range Default
Restrictions for
autotuning all PID
sets
Level
SP Mode spmd
psp: Program SP
fsp: Fixed SP
PSP
Must be set to a
fixed SP.
Adjustment
Level
AT Execute/Cancel at
ata1: All PID 40% AT
*1*2
ata2: All PID 100% AT
*1
off : AT cancel
at-1: 100% AT
at-2: 40% AT
*2
AT
Cancel
Must be set to All
PID 40% AT or All
PID 100% AT.
Fixed SP fsp
SP lower limit to SP upper
limit
0
Must be set in the
zone of the PID set
that is the autotuning
starting point.
Reset Operation rtsm
stop: Stop control
fsp: Fixed SP operation
STOP ---
Initial Setting
Level
All PID AT Upper
Limit SP
tspu
SP lower limit to SP upper
limit
0
Must be set in the
zone of the PID set
for the autotuning
ending point.
PID Set No. pid
0: Automatic selection
1 to 8: PID set 1 to 8
PID Set
1
Must be set to 0.
Program
Setting Level
PID 1 to 7 Automatic
Selection Range
Upper Limits
*3
1.aut
Temperature:
1,999 to
9,999 EU
1320
Must be set to the
upper limits of the
automatic PID set
number selection
zones for
autotuning.
PID Setting
Level
Analog:
5.0 to 105.0%
105.0
PID Set Automatic
Selection Data
pidi
pv: PV
dv
: Deviation (PV
SP)
sp: SP
PV
Must be set to PV or
SP.
Advanced
Function
Setting Level
PID Set Automatic
Selection Hysteresis
pidh 0.10 to 99.99 %FS 0.50 ---
Execution Conditions

Table of Contents

Related product manuals