6 - 63
6 Parameters
E5@C-T Digital Temperature Controllers User’s Manual (H185)
6-9 Initial Setting Level
6
This parameter sets the last SP for auto-tuning when auto-tuning all PID sets.
tspu
All PID AT Upper Limit SP
Control must be set to 2-PID control and the PID
Set Automatic Selection Data parameter must not
be set to DV (deviation).
You can set the last SP for auto-tuning when auto-tuning all PID sets.
When you auto-tune all PID sets, auto-tuning is performed from the Fixed SP value to the
All PID AT Upper Limit SP value.
If the Fixed SP value is greater than or equal to the All PID Upper Limit SP value (for
normal operation, it must be less than or equal), auto-tuning is performed only for the
Fixed SP value.
z Related Parameters
PID ON/OFF (Initial Setting Level): Page 6-63
AT Execute/Cancel (Adjustment Level): Page 6-27
Fixed SP (Adjustment Level): Page 6-28
PID * Automatic Selection Range Upper Limit (PID Setting Level): Page 6-49
Set Point Upper Limit (Initial Setting Level): Page 6-58
Set Point Lower Limit (Initial Setting Level): Page 6-58
cntl
PID·ON/OFF A Standard Model must be used.
This parameter selects 2-PID control or ON/OFF control.
The auto-tuning function can be used in 2-PID control.
z Related Parameters
AT Execute/Cancel (Adjustment Level): Page 6-27
Manual Reset Value (Adjustment Level): Page 6-38
Hysteresis (Heating) and Hysteresis (Cooling) (Adjustment Level): Page 6-38
Function
Setting
Setting range Unit Default
SP Lower Limit to SP Upper Limit EU 0
See
See
Function
Setting
Setting range Default
pid: 2-PID, onof: ON/OFF onof
See
See