6 Parameters
E5@C-T Digital Temperature Controllers User’s Manual (H185)
6-10 Advanced Function Setting Level
6
p-db
PV Dead Band A Position-proportional Model must be used.
When the PV enters the PV dead band, any unnecessary output is stopped to prevent the
valve from deteriorating.
z Related Parameters
Close/Floating, Motor Calibration, and Travel Time (Initial Setting Level): Page 6-75
Position Proportional Dead Band (Adjustment Level): Page 6-41
Open/Close Hysteresis (Adjustment Level): Page 6-42
manl
Manual MV Limit Enable
Control must be set to 2-PID control.
Close control must be used (Position-proportional
Model).
• This parameter sets whether the MV Upper Limit and MV Lower Limit parameters are to
be enabled for manual MV in Manual Mode.
z Related Parameters
MV Upper Limit (Adjustment Level): Page 6-40
MV Lower Limit (Adjustment Level): Page 6-40
PID*MV upper limit, PID*MV lower limit (PID setting level): Page 6-46
Function
SP
PV
Unnecessary output is
stopped in this range.
PV Dead Band
Setting
Setting range Unit Default
0 to 9999 EU 0
See
See
Function
Setting
Setting range Default
on: Enabled, off: Disabled off
See
See